Protective compensation chokes

Three-phase protective compensation reactors for capacitors

The three-phase protective choke limits the higher harmonic currents on the capacitors, which are used for reactive power compensation.

Protective compensation chokes meet the requirements of STN EN 60076-6.

Basic characteristic:

- input voltage 3x400V 50Hz

- thermal insulation T40/F

- protection IP00

- protection class I

- built-in bimetallic heat sensor 125°C /250V-1.5A/

 

Basic parameters

 

 

 

 

 

P

L

Heat

Current

 

(kVAr)

(mH)

loss /W/

A

Protective compensation choke

6,25

6,1

42

9

Protective compensation choke

12,5

3,1

58

18

Protective compensation choke

25

1,5

105

36

Protective compensation choke

50

0,77

155

72

 

Dimension

 

 

 

 

 

 

Type

Width

Depth

Height

 Weight

 

(kVAr)

(mm)

(mm)

(mm)

kg

Protective compensation choke

6,25

180

70

180

4,9

Protective compensation choke

12,5

180

85

180

7,5

Protective compensation choke

25

240

100

240

13

Protective compensation choke

50

300

150

250

28